Copyright ©2019 Jiangsu huatai electric instrument co., LTD
Products
Category:
Fireproof tank type and partition cable tray
Steel fireproof paint (paint) bridge
Fireproof coating:
Appearance: white, uniform thick fluid, no agglomeration;
Surface drying time: 2 hours;
Bond strength: 0.78Mpa;
Shock resistance: the deflection L/200 coating does not layer, does not fall off;
Bending resistance: the flexural L/100 coating does not layer or fall off;
Fire resistance: no change in coating after 24 hours of tap water in tap water;
Acid resistance: immersed in 3% HCL for more than 24 hours, no change in coating;
Alkali resistance: foaming in 3% Ca(OH)2 for more than 24 hours, no change in coating;
Salt tolerance: the foam was immersed in 3% NaCl for more than 24 hours, and the coating did not change;
Frost resistance: 15 times;
The coating thicknesses for different fire resistance limits are as follows:
Fire limit h 0.5 1 1.5 2 2.5
Coating thickness mm 0.4-0.6 0.8-1.0 1.4-1.6 1.8-2.0 2.4-2.6